The ZAIO-MI is both an input and output module in a modern enclosure (2 gang box size) with well protected electronic circuit board to minimize any damages during installation. It is supplied with a back box suitable for surface mount indoor installation. Designed and manufactured to meet the requirements of EN54-18 2005 and EN54-17 2005. The ZAIO-MI is used when both an input needs to be monitored and at the same time a local output (relay output) needs to be triggered to switch ancilliary equipment on or off during an alarm condition. Typical output triggering includes: controlling lift operation during an alarm, starting fire pump, stopping ventilation fans etc. For more details and connection information consult the installation guide.


1527.00 

Learn More


FEATURES


  • Loop powered (60 devices per loop as maximum) 
  • Hand addressed using the 8 way dip switch OR 
  • Softly addressed using our handheld MKII Programmer (part no. 48-004) 
  • Equipped with short circuit line isolator 
  • Extensive front unit indications


TECHNICAL SPECIFICATIONS


  • Part Number 48-108
  • Operating Voltage 17-28V DC 
  • Quiescent Current @ 24V 1.0mA 
  • Switch Input Closed (LED OFF) 1.25mA 
  • Switch Input Closed (LED ON) 3.60mA
  • Relay Rating SELV @ 1A 
  • Isolating Current 7.3mA 
  • Input End of Line 20k Alarm 
  • Triggering Resistor 1k 
  • Operating Temperature -10°C to +55°C 
  • Max Humidity 95% RH Non Condensing 
  • IP rating IP21C 
  • Size (mm) 150 x 90 x 45 
  • Weight 220g