The ZAI-MI is an input module supplied in a modern enclosure (2 gang box size) with well protected electronic circuit board to minimize any damages during installation. It is supplied with a back box suitable for surface mount indoor installation. Designed and manufactured to meet the requirement of EN54-18 2005 and EN54-17 2005. The ZAI-MI is used to monitor and raise alarm from any ancilliary equipment such as sprinkler flow switch, aspiration detectors, secondary fire control panel, beam detectors, external power supplies etc. For more details and connection information consult the installation guide.


1171.00 

Learn More


FEATURES


  • Loop powered (60 devices per loop as maximum) 
  • Hand addressed using the 8 way dip switch OR Softly addressed using our handheld 
  • MKII Programmer (part no. 48-004) 
  • Equipped with short circuit line isolator 
  • Extensive front unit indications


TECHNICAL SPECIFICATIONS


  • Part Number 48-101 
  • Operating Voltage 17-28V DC 
  • Quiescent Current @ 24V 1.0mA 
  • Switch Input Closed (LED OFF) 1.25mA 
  • Switch Input Closed (LED ON) 3.60mA 
  • Isolating Current 7.3mA 
  • Input End of Line 20k Alarm 
  • Triggering Resistor 1k 
  • Operating Temperature -10°C to +55°C 
  • Max Humidity 95% RH Non Condensing 
  • IP rating IP21C 
  • Size (mm) 150 x 90 x 45 
  • Weight 220g