DESCRIPTION C-TEC’s XFP two loop 32 zone addressable fire alarm panel offers high performance at a very competitive price. LPCB certified to EN54 parts 2 & 4, it is supplied in durable metal enclosure, offers combined keypad or keyswitch entry to Access Levels 2 and 3 and is compatible with Apollo's XP95/Discovery protocol. Ideal for use in small stand-alone applications or in larger applications due to its ability to sit on network of up to 8 XFP master panels, it is one of Europe's best-selling addressable fire panels. Packed full of engineering features - please refer to the feature list below - the XFP502/X is also fully compatible with C-TEC’s Hush Button fire alarm solution and its new range of EN54 certified addressable sounders and VADs.
FEATURES
TECHNIACAL SPECIFICATIONS
Approvals/certifications | Certified to EN54-2/4 by the LPCB (0832-CPD-0772). |
Protocol/compatibility | Apollo XP95/Discovery. |
Mains supply | 230V 50/60Hz. |
Mains rated current | 680mA maximum. |
Internal power supply | 27Vdc nominal. |
Total output current limited to | 3A @ 230Vac (Imax.A 270mA; Imin. 70mA). |
Quiescent current | 100mA (2 loops unloaded). |
Max battery size and type | 2 x 12V 7Ah VRLA connected in series. |
No. of loop drivers | 2. |
Max. loop output current | 500mA (25V min; 34V max). |
Max. loop length | 1KM. |
Max. addressable devices per loop | 126. |
No. of conventional sounder circuits | 2 (Max. length per circuit is 500m). |
EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Max. sounder output current | 400mA. |
Auxiliary relays | 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc. |
Other outputs | 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA. |
Auxiliary inputs | 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching). |
PC connection | PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available. |
Indicators | 2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault. |
Connections | Fixed, largest acceptable conductor size 1mm2. |
Expansion connections | 2-wire RS485 network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network). |
Product dimensions (mm) | 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). |
Construction & finish | Metal. |
IP Rating | IP30. |
Weight | 4.5kg (without batteries). |