FEATURES
- Third-party certified to EN54-2/4 by the Loss Prevention Certification Board (LPCB).
- Compatibility with Apollo's XP95/Discovery protocol.
- Two independently programmable conventional sounder circuits.
- Two programmable inputs.
- A fault output relay and three programmable relay outputs with voltage free changeover contacts.
- A selection of zone dependency/coincidence functions.
- A day/night (building occupied/unoccupied) function.
- An investigation delay period function.
- Phased evacuation facility.
- An alarm counter that records how many times the panel has been in alarm state.
- Powerful short circuit protected loop drivers, capable of supporting up to 40 loop powered 10mA sounders per loop.
- An integral EN54-4/A2 switch mode power supply.
- Adjustable contamination levels.
- Earth fault monitoring.
- Combined keypad / keyswitch entry to Access Levels 2 and 3.
- 999 event monitoring.
- An intuitive Windows based upload-download PC program.
- Optional flush-mounting bezel and glazed stainless steel enclosure also available.
- Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 non-redundant network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main pane
TECHNICAL SPECIFICATIONS
Approvals/certifications | Certified to EN54-2/4 by the LPCB (0832-CPD-TBC). | Protocol/compatibility | Apollo XP95/Discovery. | Mains supply | 230V 50/60Hz. | Mains rated current | 680mA maximum. | Internal power supply | 27Vdc nominal. | Total output current limited to | 3A @ 230Vac (Imax.A 250mA; Imin. 70mA). | Quiescent current | 80mA (loop unloaded). | Max battery size and type | 2 x 12V 7Ah VRLA connected in series. | No. of loop drivers | 1. | Max. loop output current | 500mA (25V min; 34V max). | Max. loop length | 1KM. | Max. addressable devices per loop | 126. | No. of conventional sounder circuits | 2 (Max. length per circuit is 500m). | EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). | Max. sounder output current | 400mA. | Auxiliary relays | 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc. | Other outputs | 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA. | Auxiliary inputs | 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching). | PC connection | PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available. | Indicators | 2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault. | Connections | Fixed, largest acceptable conductor size 1mm2. | Expansion connections | 2-wire RS485 non-redundant network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network). | Product dimensions (mm) | 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). | Construction & finish | Metal. | IP Rating | IP30. | Weight | 4.5kg (no batteries). | Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
|
|
|
|
MOUNTING INFORMATION
Product dimensions: | 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). | Hole required for semi-flush mounting: | 412 W x 255 H x 50 D mm. Requires XFP385 bezel |
|
|
|
|
DATASHEETS
C-TEC_(Computionics_Limited)_-_XFP502_X_Datasheet_2020-04-03-091655.pdf