The Sigma CP range consists of a series of conventional fire alarm control panels designed in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment. This Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder circuits are provided). Wiring sounders to the detection circuits eliminates the need to install sounder circuit cables and also offers the ability to provide zoned or two stage sounder operation. All control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of BS EN54-4.
FEATURES
TECHNICAL SPECIFICATION
FREQUENTLY ASKED QUESTIONS
What End Of Line Resistors does the Sigma CP Require?
The Detection Zones on the Sigma CP Conventional require a 6K8 End of Line resistor. The Sounder Output requires a 10K5 End of Line Resistor.
Can A Fault From The Sigma CP Power Supply Be Monitored Remotely?
Yes, by taking a pair of cables from the ROV and the FLT and then connect these across the common and normally closed of the fault relay, anytime that fault relay goes closed this will put a short across the input and put a fault on the Kentec Sigma CP panels.
DATASHEET