The EX Pro is a robust & reliable single zone extinguishing panel housed in a modern enclosure. The panel includs a blue 4 x 20 LCD display with a list of extra features such as memory log of fire, fault & system events, adjustable flood times and countdown of extinguishing sequence. The system is fully comliant with EN54 parts 2 & 4, and EN 12094 part 1.


10479.00 

ENCLOSURE: *

Learn More


FEATURES


  • Single extinguishing zone
  • LCD display for simple setup
  • Optional 8-way relay output board
  • Compact repeater available with LED indication & manual release trigger
  • 1.0A bottle output
  • Integrated 2.0 Amp power supply
  • Complies with EN54 parts 2 & 4, and EN 12094 part 1


TECHNICAL SPECIFICATION


  • General
    • Supply Voltage: 230 AC +/- 10%
    • Battery Space: Up to 2 x 7.0 AH, 12V DC SLA batteries
    • IP Rating: IP32
    • Operating Temperature: -10 to 50°C
    • Box Dimensions (mm): (W) 370 x (H) 311 x (D) 113
  • Detection Zones
    • Zone Capacity: 32 Devices
    • Number of Detection Zones: 2 - EOL (4.7k)
    • Line Monitoring for Open & Short Circuit: Yes
    • Max Cable Length Per Zone: 250m
    • Zone Quiescent Current: 2mA max - EOL
  • Sounder Outputs
    • Number of Sounder Circuits: 3 (S1A, S1B for 1st Stage, S2 for 2nd Stage)
    • Sounder Output Rating: 21-28 VDC, fused at 150mA per circuit
    • Max Cable Length: 60m
  • Auxilliary Outputs
    • Number of Auxilliary Outputs: 5 (fault, 1st stage fire, 2nd stage fire, extract fan, gas fired output)
    • Relay Rating: (30V - 1 Amp)
  • Extinguishant Release Outputs
    • Bottle Output: 1.0 Amp - EOL 18K
    • 5 Monitored Inputs: Manual release, low pressure, gas fired, auto input & abort
    • EOL Value: 18K


DATASHEET