Zeta Alarm Systems is proud to introduce the most advanced 2 wire system on the market. We can now provide a system that gives all of the benefits associated with a ‘2 Wire’ installation (less cable, quicker installation, cost savings on labour/ product) and has the facility to ‘I.D.’ the devices. The system is built on the proven communication protocol developed by Zeta Alarm Systems and shares the same platform as our largest, most powerful system.The ID2 can be used for new installations, as a retrofit for any conventional system or as a replacement for existing 2 wire systems when the extra features are deemed to be desirable/necessary. This is possible because the ID2 devices sit on radial circuits, thus making it easy to ‘upgrade’ a system with the facility to I.D. devices without the need to re-wire.


8333.00 

Learn More


FEATURES 


  • One man walk test facility
  • Ability to isolate zones/sounder circuits
  • High visibility blue LCD screen as standard
  • Deeper version panel available if larger batteries required
  • Full range of zone powered devices available
  • Auto configuration for easy set up
  • Safer than a traditional 2 wire/conventional system as it tells you exactly where the event is - no time wasted searching a whole zone
  • System already wired as a loop? No problem! Just select ‘Loop Mode’ in the panel


TECHNICAL SPECIFICATION


  • Detection Zones: 2-8 Zones
  • Mains Voltage: 230V AC +10% /- 15% @ 50/60 Hz
  • System Voltage: 29V DC Nominal (19 – 30 V)
  • Sounder Alarm Output: Loop Powered Sounders 2 x Conventional sounder circuits 28V nominal,150mA (20-30V DC)
  • Fault Output: 1 x Fault Relay SELV@1A (Normaly Energised
  • Fire Relay Output: 1 x Fire Relay SELV@1A
  • Zone Capacity: 15 Devices Per Zone
  • Max. No. of Detection Circuits: Radial Mode - 8 Radial Circuits Loop Mode - 1 Loop Circuit
  • Max. Loop Sounder Quantity: 80 Sounders
  • Repeater Connection: RS485
  • Dimensions (mm): 370(W) x 311(H) x 113(D)


DATASHEET


Infinity-ID2-Panels.pdf