The ICAM ILS systems provide Laser Air-sampling Smoke Detection solutions to meet the unique needs of numerous commercial and industrial applications. ILS systems are suitable for both medium sensitivity and multi- hole Class C applications.


19470.00 

CHANNELS : *

Learn More


FEATURES


  • Single or dual channel smoke detection.
  • Laser air-sampling smoke detection.
  • Multiple detection strategies.
  • 100m (328 ft) per sampling pipe.
  • Microprocessor controlled and programmed.
  • Highest fan capacity in its class.
  • Integral display and programmer.
  • Field serviceable air filter.
  • Adjustable aspirator speed with airflow monitoring.
  • IP65 enclosure.


TECHNICAL SPECIFICATIONS


  • EN54-20 Sensitivity (holes per pipe)
    • Class A : 3 holes
    • Class B : 6 holes
    • Class C : 18 holes
  • Integrate Detectors : 1 or 2 laser spot (point) detectors
  • Supply Voltage : 24 VDC nominal (18 to 30 VDC)
  • Current : 300 mA (max)
  • Dimensions (WHD) : 259 mm x 184 mm x 166 mm (10.2 in. x 7.2 in. x 6.5 in.)
  • Operating Conditions :
    • Temperature: -10 to 50°C (14 to 122°F)
    • Humidity: 10 to 95% RH (noncondensing)
  • Inlet Pipe Size :
    • Outer Diameter: 25 mm (0.98 in.)
    • Inner Diameter: 21 mm (0.83 in.)
  • Sampling Network : Pipe Length: Up to 100 m (328 ft) per inlet
  • Sensitivity : 0.06 to 6.0 % obs/m (0.02 to 1.83 % obs/ft)
  • IP Rating : IP65
  • Filtration : Serviceable filter (External filter optional)
  • Flow Monitoring and Reporting : High and Low adjustable
  • Fan Control : 10 programmable speeds
  • Relays : Contacts rated at 1A @ 30 VDC, NO/NC
    • ILS-1 : Action, Fire, Fault (3 Relays)
    • ILS-2 : 
      • Detector 1 - Action, Fire, Fault (3 Relays)
      • Detector 2 - Action, Fire, Fault (3 Relays)
  • Cable Termination :
    • Power Supply : 18 AWG min. (16 x 0.25 mm dia.)
    • Field Connections : 11 AWG max. (2.5 mm dia.)
    • USB : Standard USB cable for Type B USB connector


DATASHEET


ICAM-ILS.pdf