The Xenex conventional fire detection and alarm system from Gent provides owners of small building premises with quality protection equipment at an economical price. The Xenex panel complies fully with the European standard EN 54 Parts 2 and 4 and can be used on installations meeting BS 5839-1. Each panel contains its own integral power supply and battery support for up to eight alarm sounder circuits, two auxiliary relay contacts, a zone disablement facility and a one man test and commission facility, all simplifying system design, installation and commissioning.
FEATURES
TECHNICAL SPECIFICATIONS
Approval | BSI Approved (KM 553763) |
Battery | 2 x 12V, 2.1 Ah min |
Battery Standby | 72 hours (1mA per zone + 0.5A sounder load max) |
CPD Number | 0086-CPD-553764 |
Cable Type | BS 6387, 2 core, min 1.5mm2 CSA |
Class Change Facility | Volt free contact - max distance 100m |
Maximum Load Per Zone | 3mA |
Maximum Sounder Circuit Load | 500mA per circuit max 1A combined |
Number Of Sounder Circuits | 2 |
Operating Temperature | Indoor, 0 - 40ºC |
Relevant Standard | EN54: Parts 2 &4 |
Weight | 5.8Kg |
DATASHEET