DESCRIPTION The Discovery Marine Manual Call Point (MCP) is based on the KAC conventional MCP range. It is electronically and mechanically compatible with previous Apollo call points based on KAC’s World Series product. The address of each call point is set at the commissioning stage by means of a seven-segment DIL switch. If an MCP is activated, it interrupts the normal protocol to give a fast response. A single bi-coloured alarm LED is provided on the manual call point. This LED is controlled, independently of the call point, by the control panel and may be set to flash each time the call point is polled. The red LED is illuminated when the call point has been activated and sent into alarm. On the isolated versions an amber/yellow LED indicates a short-circuit on the loop wiring either side of the call point. Call points can be remotely tested from the panel by transmission of a single bit in the communications protocol. Call points respond by providing a value of 64 which corresponds to the alarm value. The panel should recognise this response as a test signal and should not raise a general alarm.


1717.00 

Learn More


FEATURES


  • Flashing LED option to indicate polling (Discovery systems only)
  • ‘Plug and Play’ terminal connections for fast wiring
  • Continuity link for wiring test before commissioning
  • Reports an alarm in under 0.2 seconds
  • Resettable element


TECHNICAL SPECIFICATION


  • Power-Up Surge Current: 1mA
  • Maximum Power-Up Time: Commercial
  • Quiescent Current: 100μA
  • Humidity (Min): 95% RH
  • Humidity (Max): 0% RH
  • Operating Temperature (Min): -20°C - +60°C
  • IP Rating: IP24D
  • Colour: Red


DATASHEET